Mô tả
RowCool 70kW
HCH1CB0 with reheater/humidifier
Maximum cooling capacity *1
70 kW
Sensible cooling capacity
69.3 kW
Input power
3Φ4 W+G/50,60 Hz/ 380 V
Maximum input power
HCH1CB0: 3 kW
HCH1CB0 with reheater/humidifier: 14 kW
Maximum current
HCH1CB0: 5 AMP
HCH1CB0 with reheater/humidifier: 22 AMP
Air flow
11400 CMH (6700 CFM)
Reheater
(HCH1CB0 with reheater/humidifier)
Capacity
8.1 kW (27600 Btu/HR)
Humidifier
(HCH1CB0 with reheater/humidifier)
Power consumption
2.25 kW
Filter classe
30-35 % MERV8
Inlet water
32 A mm (1 1/4 in) PT thread female
Outlet water
32 A mm (1 1/4 in) PT thread female
Drain pipe
20 A mm (3/4 in) PT thread male
Humidifier supply water
HCH1CB0 with reheater/humidifier:10 A mm (3/8 in)PT thread male
Connections of inlet/outlet water
Bottom / Top(optional)
Power Wiring
Both at top and bottom
Communication Interface
SNMP slot x1 (SNMP card is optional), RS232x1, RS485x1 (Modbus protocol), Input dry contact x2, Output dry contact x2, Temperature sensor x3, Remote temperature/humidity sensor x1
Accessories
SNMP card, Connection tube for top tubing, Humidifier accessory kit, reheater accessory kit, Remote temperature/humidity sensor, Drain Pump, Washable filter
Height (wo/w packaging)
2000 / 2220 mm
Width (wo/w packaging)
600 / 764 mm
Depth (wo/w packaging)
1090 / 1342 mm
Weight (Gross / Operating)
HCH1CB0: 368 / 414 kg
HCH1CB0 with reheater/humidifier: 375 / 421 kg
Please contact Delta or a local distributor for new specifications regarding the constant improvements Delta makes for various lines of products.
1. Testing standard of cooling capacity at 60Hz
Returned air |
40.6°C (DB) / 21.6°C(WB) |
Incoming chilled water temperature |
7.2 °C |
Temperature difference of inlet and outlet chilled water |
8.8 °C |
|
2. Reference for cooling capacity testing: ASHARE 127 and GB/T 19413-2003
3. Operation conditions: inlet water temperature 5~15°C, return air temperature 4~40°C DB, 30~85% non-condensing
4. Specifications are subject to change due to constant product updates
RowCool 95kW
HCH1CD0 with Humidity Control
Power
Input power : 3N~, 380V, 50/60Hz
Power consumption : 4.8kW
Rating capacity *
Capacity : 95.9 kW
Sensible Capacity : 95.9 kW
Max capacity **
Capacity : 122.7 kW
Sensible Capacity : 122.7 kW
Capacity at high inlet water ***
Capacity : 81.2 kW
Sensible Capacity : 81.2 kW
Valve
Air flow : 14050 m3/h
Inlet water temp. range : 5~22°C
Reheater
Type : Electric heater
(HCH1CD0 with Humidity Control)
Capacity : 8.1 kW
Humidifier
Type : Electrode
(HCH1CD0 with Humidity Control)
Capacity : 3 kg/h
Connection
Inlet pipe : 1 1/4” PT Female
Outlet pipe : 1 1/4” PT Female
Dimension (W x D x H)
600 x 1090 x 2000 mm
HCH1CD0 with Humidity Control : 422 kg
* Operation conditions: 40.6°C (DB), 21.6°C (WB), inlet water temperature 7°C, rated water flow
** Operation conditions: 48.9°C (DB), 23.9°C (WB), inlet water temperature 7°C, maximum water flow
*** Operation conditions: 40.6°C (DB), 21.6°C (WB), inlet water temperature 12°C, temperature difference 9°C
Đánh giá