Technical Specification
Model | DXA-60 (In) DXA-100 (In) | |||
Power Supply | 380V 3Ph – 50Hz | |||
Air Discharge | Upflow / Downflow | |||
Performance | 1. Return air condition : 24℃, 50% RH, outdoor temperature 35℃
Total Cooling Capacity (kW) 65.8 Sensible Cooling Capacity (kW) 59.3 |
100.2 90.6 |
||
2. Return air condition : 24℃, 50% RH, outdoor temperature45℃
Total Cooling Capacity (kW) Sensible Cooling Capacity (kW) |
57.8 52 |
90.5 85 |
||
Quantity of Compressor | 2 | 2 | ||
Indoor Fan | Airflow (m3/h)
Quantity of Fan |
17000
2 |
23000
3 |
|
Reheat | Capacity (kW) | 9 | 9 | |
Humidifier | Capacity (kg/h) | 10 | 10 | |
Piping | Liquid Pipe – OD (mm)
Gas Pipe – OD (mm) Inlet Pipe of Humidifier (Female) Drain Pipe – ID (mm) |
16
22 G1/2″ 25 |
19
22 G1/2″ 25 |
|
Physical | Width (mm)
Depth (mm) Height (mm) Weight (kg) |
2100
890 1990 670 |
2500
890 1990 900 |
|
Breakers & Cables | ||||
Indoor Unit
Outdoor Unit |
Recommended Air Break Switch (A)
Cables (mm2) |
100
16 |
125
25 |
|
Recommended Air Break Switch (A)
Cables (mm2) |
20
2.5 |
20
2.5 |
||
Outdoor Condenser Type and Qty | CS54 x 2 | CS78 x 2 | ||
Remark:
- EC fan configured as standard.
- Electric expansion valve as standard.
- For modularized system, fan quantity is 2.
Outdoor Condenser
Model | Quantity of fan (s) | Length (mm) | Height (mm) | Width (mm) | Weight (kg) | Liquid Line-OD (mm) | Hot Gas Line-OD (mm) |
DXA-60 (out) | 1 | 1910 | 1270 | 653 | 50 | 19 | |
DXA-100 (out) | 2 | 2410 | 1270 | 653 | 00 | 19 | 28 |